ModelIndoor FDE100VH
Outdoor FDC100VNP
Power SourcePh/V/Hz1 / 220-240 / 50
Nominal Cooling CapacityMin~Max kW10.0 ( 2.8 ~ 11.2 )
Nominal Heating CapacityMin~Max kW11.2 ( 2.5 ~ 12.5 )
Power ConsumptionCooling/Heating kW2.66 / 2.94
COPCooling/Heating 3.76 / 3.81
Inrush CurrentA5
Max. CurrentA21
Sound Power LevelIndoor (Cooling/Heating) dB(A)64 / 64
Outdoor (Cooling/Heating) dB(A)70 / 70
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)34 - 48 / 34 - 48
Outdoor (Cooling/Heating) dB(A)57 / 61
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min32 - 16.5 / 32 - 16.5
Outdoor (Cooling/Heating) m3/min75 / 79
Dimension (H x W x D)Indoor mm250 x 1,620 x 690
Outdoor mm845 x 970 x 370
Net WeightIndoor kg43
Outdoor kg70
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8") / 15.88(5/8")
Max. Piping Lengthm30
Max. Piping Height Differencem20
Outdoor Operating Temperature RangeCooling °CDB -15~46
Heating °CDB -15~20