CATEGORIES
FDE200VSAPVH

Motion Sensor (Option)

Flap Control System

ModelIndoor FDE100VH x 2
Outdoor FDC200VSA
Power SourcePh/V/Hz3 / 380-415 / 50
Nominal Cooling CapacityMin~Max kW19.0 ( 5.2 ~ 22.4)
Nominal Heating CapacityMin~Max kW22.4 ( 3.3 ~ 25.0 )
Power ConsumptionCooling/Heating kW6.34 / 6.10
COPCooling/Heating 3.00 / 3.67
Inrush CurrentA5
Max. CurrentA20
Sound Power LevelIndoor (Cooling/Heating) dB(A)64 / 64
Outdoor (Cooling/Heating) dB(A)72 / 74
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)34 - 48 / 34 - 48
Outdoor (Cooling/Heating) dB(A)58 / 59
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min32 - 16.5 / 32 - 16.5
Outdoor (Cooling/Heating) m3/min135 / 135
Dimension (H x W x D)Indoor mm250 x 1,620 x 690
Outdoor mm1,300 x 970 x 370
Net WeightIndoor kg43
Outdoor kg115
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8") / 22.22(7/8")
Max. Piping Lengthm70
Max. Piping Height Differencem30 (Higher) / 15(Lower)
Outdoor Operating Temperature RangeCooling °CDB -15~50
Heating °CDB -15~20