CATEGORIES
FDF140VSAPVD1

Wide and Powerful Air Flow

Easy Transportation and Installation Workability

ModelIndoor FDF71VD1 x 2
Outdoor FDC140VSA
Power SourcePh/V/Hz3 / 380-415 / 50
Nominal Cooling CapacityMin~Max kW13.6 ( 5.0 ~ 14.5 )
Nominal Heating CapacityMin~Max kW15.5 ( 4.0 ~ 16.5 )
Power ConsumptionCooling/Heating kW5.15 / 4.35
COPCooling/Heating 2.64 / 3.56
Inrush CurrentA5
Max. CurrentA15
Sound Power LevelIndoor (Cooling/Heating) dB(A)61 / 61
Outdoor (Cooling/Heating) dB(A)73 / 73
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)33 - 42 / 33 - 42
Outdoor (Cooling/Heating) dB(A)57 / 59
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min18 - 12 / 18 - 12
Outdoor (Cooling/Heating) m3/min75 / 73
Dimension (H x W x D)Indoor mm1,850 x 600 x 320
Outdoor mm845 x 970 x 370
Net WeightIndoor kg49
Outdoor kg82
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8") / 15.88(5/8")
Max. Piping Lengthm50
Max. Piping Height Differencem50 (Higher) / 15(Lower)
Outdoor Operating Temperature RangeCooling °CDB -15~50
Heating °CDB -20~20