CATEGORIES
FDT140VNXVH

Draft Prevention Panel (Option)

Motion Sensor (Option)

Individual Flap Control System

ModelIndoor FDT140VH
Outdoor FDC140VNX
Power SourcePh/V/Hz1 / 220-240 / 50 ; 220 / 60
Nominal Cooling CapacityMin~Max kW14.0 (5.0~16.0)
Nominal Heating CapacityMin~Max kW16.0 (4.0~18.0)
Power ConsumptionCooling/Heating kW4.58 / 4.20
COPCooling/Heating 3.06 / 3.81
Inrush CurrentA5
Max. CurrentA26
Sound Power LevelIndoor (Cooling/Heating) dB(A)63 / 64
Outdoor (Cooling/Heating) dB(A)72 / 72
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)32-48 / 31-48
Outdoor (Cooling/Heating) dB(A)72 / 72
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min38-19 / 38 - 19
Outdoor (Cooling/Heating) m3/min100 / 100
Dimension (H x W x D)Indoor mmUnit:298 x 840 x 840 / Panel: 35 x 950 x950
Outdoor mm1300 x 970 x 370
Net WeightIndoor kg30(Unit:25 Standard Panel:5)
Outdoor kg105
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8”) / 15.88(5/8”)
Max. Piping Lengthm100
Max. Piping Height Differencem30 (Higher) / 15(Lower)
Outdoor Operating Temperature RangeCooling °CDB -15~43
Heating °CDB -20~20