CATEGORIES
FDT140VSXTVH

Draft Prevention Panel (Option)

Motion Sensor (Option)

Individual Flap Control System

ModelIndoor FDT50VH x 3
Outdoor FDC140VSX
Power SourcePh/V/Hz3 / 380-415 / 50 ; 380 / 60
Nominal Cooling CapacityMin~Max kW14.0 ( 5.0 ~ 16.0 )
Nominal Heating CapacityMin~Max kW16.0 ( 4.0 ~ 20.0 )
Power ConsumptionCooling/Heating kW3.93 / 4.00
COPCooling/Heating 3.56 / 4.00
Inrush CurrentA5
Max. CurrentA15
Sound Power LevelIndoor (Cooling/Heating) dB(A)55 / 56
Outdoor (Cooling/Heating) dB(A)72 / 72
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)26 - 41 / 20 - 42
Outdoor (Cooling/Heating) dB(A)49 / 52
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min22 - 10 / 22 - 10
Outdoor (Cooling/Heating) m3/min100 / 100
Dimension (H x W x D)Indoor mmUnit: 236 x 840 x 840 Panel: 35 x 950 x 950
Outdoor mm1,300 x 970 x 370
Net WeightIndoor kg24(Unit:19 Standard Panel:5)
Outdoor kg105
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8") / 15.88(5/8")
Max. Piping Lengthm100
Max. Piping Height Differencem30 (Higher) / 15(Lower)
Outdoor Operating Temperature RangeCooling °CDB 15~43
Heating °CDB -20~20