CATEGORIES
FDU100VNP1VH

External Static Pressure (E.S.P) Control

Motion Sensor (Option)

ModelIndoor FDU100VH
Outdoor FDC100VNP
Power SourcePh/V/Hz1 / 220-240 / 50
Nominal Cooling CapacityMin~Max kW10.0 ( 2.8 ~ 11.2 )
Nominal Heating CapacityMin~Max kW11.2 ( 2.5 ~ 12.5 )
Power ConsumptionCooling/Heating kW3.00 / 2.93
COPCooling/Heating 3.33 / 3.82
Inrush CurrentA5
Max. CurrentA22
Sound Power LevelIndoor (Cooling/Heating) dB(A)65 / 65
Outdoor (Cooling/Heating) dB(A)70 / 70
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)30 - 44 / 30 - 44
Outdoor (Cooling/Heating) dB(A)57 / 61
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min36 - 19 / 36 - 19
Outdoor (Cooling/Heating) m3/min75 / 79
External Static PressurePaStandard:60 Max:200
Dimension (H x W x D)Indoor mm280 x 1,370 x 740
Outdoor mm845 x 970 x 370
Net WeightIndoor kg54
Outdoor kg70
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8") / 15.88(5/8")
Max. Piping Lengthm30
Max. Piping Height Differencem20
Outdoor Operating Temperature RangeCooling °CDB -15~46
Heating °CDB -15~20