External Static Pressure (E.S.P) Control
Motion Sensor (Option)
Model | Indoor | FDUM60VH x 2 | |
Outdoor | FDC125VNX | ||
Power Source | Ph/V/Hz | 1 / 220 - 240 / 50 | |
Nominal Cooling Capacity | Min~Max | kW | 12.5 ( 5.0 ~ 14.0 ) |
Nominal Heating Capacity | Min~Max | kW | 14.0 ( 4.0 ~ 17.0 ) |
Power Consumption | Cooling/Heating | kW | 3.26 / 3.66 |
COP | Cooling/Heating | 3.83 / 3.83 | |
Inrush Current | A | 5 | |
Max. Current | A | 26 | |
Sound Power Level | Indoor (Cooling/Heating) | dB(A) | 60 / 60 |
Outdoor (Cooling/Heating) | dB(A) | 70 / 70 | |
Sound Pressure Level (Lo – Hi) | Indoor (Cooling/Heating) | dB(A) | 25-36 / 25-36 |
Outdoor (Cooling/Heating) | dB(A) | 48 / 50 | |
Air Flow (Hi - Lo) | Indoor (Cooling/Heating) | m3/min | 20 - 10 / 20 - 10 |
Outdoor (Cooling/Heating) | m3/min | 100 / 100 | |
External Static Pressure | Pa | Standard:35 Max:100 | |
Dimension (H x W x D) | Indoor | mm | 280 x 950 x 635 |
Outdoor | mm | 1,300 x 970 x 370 | |
Net Weight | Indoor | kg | 34 |
Outdoor | kg | 105 | |
Refrigerant Piping Size | Liquid / Gas | mm(in) | 9.52(3/8") / 15.88(5/8") |
Max. Piping Length | m | Max.100 | |
Max. Piping Height Difference | m | Max.30 | |
Outdoor Operating Temperature Range | Cooling | °CDB | -15~43 |
Heating | °CDB | -20~20 |