| Model | Indoor | FDUM71VH x 2 | |
| Outdoor | FDC140VNX | ||
| Power Source | Ph/V/Hz | 1 / 220 - 240 / 50 | |
| Nominal Cooling Capacity | Min~Max | kW | 14.0 ( 5.0 ~ 16.0 ) |
| Nominal Heating Capacity | Min~Max | kW | 16.0 ( 4.0 ~ 18.0 ) |
| Power Consumption | Cooling/Heating | kW | 4.36 / 4.35 |
| COP | Cooling/Heating | 3.21 / 3.68 | |
| Inrush Current | A | 5 | |
| Max. Current | A | 26 | |
| Sound Power Level | Indoor (Cooling/Heating) | dB(A) | 65 / 65 |
| Outdoor (Cooling/Heating) | dB(A) | 65 / 65 | |
| Sound Pressure Level (Lo – Hi) | Indoor (Cooling/Heating) | dB(A) | 25-38 / 25-38 |
| Outdoor (Cooling/Heating) | dB(A) | 49 / 52 | |
| Air Flow (Hi - Lo) | Indoor (Cooling/Heating) | m3/min | 24 - 10 / 24 - 10 |
| Outdoor (Cooling/Heating) | m3/min | 100 / 100 | |
| External Static Pressure | Pa | Standard:35 Max:100 | |
| Dimension (H x W x D) | Indoor | mm | 280 x 950 x 635 |
| Outdoor | mm | 1,300 x 970 x 370 | |
| Net Weight | Indoor | kg | 34 |
| Outdoor | kg | 105 | |
| Refrigerant Piping Size | Liquid / Gas | mm(in) | 9.52(3/8") / 15.88(5/8") |
| Max. Piping Length | m | Max.100 | |
| Max. Piping Height Difference | m | Max.30 | |
| Outdoor Operating Temperature Range | Cooling | °CDB | -15~43 |
| Heating | °CDB | -20~20 | |