CATEGORIES
FDUM200VSATVH

External Static Pressure (E.S.P) Control

Motion Sensor (Option)

ModelIndoor FDUM71VH x 3
Outdoor FDC200VSA
Power SourcePh/V/Hz3 / 380-415 / 50
Nominal Cooling CapacityMin~Max kW19.0 ( 5.2 ~ 22.4 )
Nominal Heating CapacityMin~Max kW22.4 ( 3.3 ~ 25.0 )
Power ConsumptionCooling/Heating kW6.46 / 6.15
COPCooling/Heating 2.94 / 3.64
Inrush CurrentA5
Max. CurrentA22
Sound Power LevelIndoor (Cooling/Heating) dB(A)65 / 65
Outdoor (Cooling/Heating) dB(A)72 / 74
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)25 - 38 / 25 - 38
Outdoor (Cooling/Heating) dB(A)58 / 59
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min24 - 10 / 24 - 10
Outdoor (Cooling/Heating) m3/min135 / 135
External Static PressurePaStandard:35 Max:100
Dimension (H x W x D)Indoor mm280 x 950 x 635
Outdoor mm1,300 x 970 x 370
Net WeightIndoor kg34
Outdoor kg115
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8") / 22.22(7/8")
Max. Piping Lengthm70
Max. Piping Height Differencem30 (Higher) / 15(Lower)
Outdoor Operating Temperature RangeCooling °CDB -15~50
Heating °CDB -15~20