CATEGORIES
SRK140VNXTZSX

Jet Air Technology

Long Reach Air Flow

Flap Control System

ModelIndoor SRK50ZSX-W x 3
Outdoor FDC140VNX
Power SourcePh/V/Hz1 / 220-240 / 50
Nominal Cooling CapacityMin~Max kW14.0 ( 5.0 ~ 16.0 )
Nominal Heating CapacityMin~Max kW16.0 ( 4.0 ~ 18.0 )
Power ConsumptionCooling/Heating kW3.98 / 3.68
COPCooling/Heating 3.52 / 4.35
Inrush CurrentA5
Max. CurrentA26
Sound Power LevelIndoor (Cooling/Heating) dB(A)59 / 62
Outdoor (Cooling/Heating) dB(A)72 / 72
Sound Pressure Level (Lo – Hi)Indoor (Cooling/Heating) dB(A)22 - 44 / 23 - 46
Outdoor (Cooling/Heating) dB(A)49 / 52
Air Flow (Hi - Lo)Indoor (Cooling/Heating) m3/min14.3 - 5.4 / 17.3 - 6.2
Outdoor (Cooling/Heating) m3/min100 / 100
Dimension (H x W x D)Indoor mm305 x 920 x 220
Outdoor mm1,300 x 970 x 370
Net WeightIndoor kg13
Outdoor kg105
Refrigerant Piping SizeLiquid / Gas mm(in)9.52(3/8") / 15.88(5/8")
Max. Piping Lengthm100
Max. Piping Height Differencem30 (Higher) / 15(Lower)
Outdoor Operating Temperature RangeCooling °CDB -15~43
Heating °CDB -20~20